HI8711 Dual Setpoint - pH analog Controller with 4 to 20mA

Product Code : HI8711

Category : pH (Meters)

Catalog : sorry not ready

Product information "HI8711 Dual Setpoint - pH analog Controller with 4 to 20mA"

Inputs: BNC connector,  Direct wire connection with amplified probe (supports HI 1006 series probes) and 4-20 mA from a transmitter

  • Auto-diagnostics to verify offset and slope calibration and electrode contamination/deterioration
  • Selectable manual ON, OFF and automatic dosing control for alkaline, acid and REDOX dosing with indicator
  • Dual set point with two independent dosing outputs
  • Extended temperature compensation range: -20 to 100°C
  • Supports potential matching pin connection
  • Both 4-20 and 0-20 mA output     
  • ±5V outputs for amplified electrodes
  • Fail Safe Function–the alarm relay is activated at power down
  • Operational mode LED indicators
  • Backlit LCD
  • Transparent splash-proof cover

 

HI 8711 allows the selection of two set points with two independent outputs for acid and alkaline dosages.

Each model accepts either a direct input from a pH or ORP electrode or from a transmitter through 4-20 mA input. The instrument also provides ±5V power output and input terminals for amplified electrodes. In addition, you can choose the output configuration for connecting a recorder or a PLC, between 0-20 or 4-20 mA.

The HI 8711 incorporates adjustable overtime dosing protection from 5 to 60 minutes. If dosing exceeds selected time, the alarm will be triggered and the dosing contact will deactivate. This feature can be activated or deactivated.

 

Order Information:
The HI 8711 is supplied with mounting brackets and instructions.

 

Specification :

Range   0.00 to 14.00 pH
Resolution   0.01 pH
Accuracy
@ 20 °C
  ±0.02 pH (0 to 100 °C)
±0.05 pH (-20 to 0 °C)
±0.5% (input from transmitter)
Input   high impedance 1012 Ohm; reference and matching pin inputs are available; 4-20 mA
Power Output   ±5 Vcc; 150 mA max load for amplified electrodes
Calibration   offset: ±2 pH with OFFSET trimmer
slope: 80 to 110% with SLOPE trimmer
Temperature
Compensation
  fixed or automatic with Pt100, from -20 to 100°C (-4 to 212°F)
Recorder Output   0-20 mA or 4-20 mA (isolated)
Setpoint Relay   2, isolated, 2 A, max 240 V, resistive load, 1000000 strokes (not fuse protected)
Setpoint Range   alk. set: from 0.00 to 14.00 pH
acid set: from 0.00 to 14.00 pH
Alarm Relay   1, isolated, 2 A, max 240 V, resistive load, 1000000 strokes (not fuse protected)
Alarm Range   0.2 to 3.00 pH
Dosing Control   OFF/AUTO/ON with selection switch
Over Dosing Control   adjustable, from 5 min to 60 min with knob or disable by wire strap - on rear panel
Backlight   continuous on
Power Supply   115 VAC ±10% or 230 VAC ±10%; 50/60 Hz
Enclosure   flame retardant ABS body and front panel; transparent splash-proof front cover
Environment   -10 to 50°C (14 to 122°F); RH max 95% non-condensing
Panel Cutout   141 x 69 mm (5.6 x 2.7")
Weight   1 kg (2.2 lb.)